Input |
• Rated input voltage |
115/230Vac ±15%, jumper on pcb90÷264Vac with PFC |
|
• Line frequency |
50/60Hz |
|
• Leakage current to GND (max) |
Max 2mA at 50Hz |
|
• Input protection |
• Start-up peak current limitation : 30A at Vin=220Vac• Fuses on both input lines and EMI filter |
Output |
• Output voltage |
384W |
|
• Output voltage temp drift |
0.01%/°C typ. |
|
• Output voltage long term stability |
Better than 1% after 24 hours |
|
• Adjustable voltage range |
• Vadjust trimmer on front panel |
|
• Remote sense compensation |
0.5V max |
|
• Output power (max) |
390W |
|
• Temp power derating |
2%/°C (50÷70°C) |
|
• Hold up time |
15msec min. |
|
• Test points |
Vout test-points on front panel |
|
• Output protections |
• Overload• Short circuit• Overvoltage : at Vo + 25% typ.• Over temperature: shutdown above 95°C |
|
• Output signals |
• Alarm relay contact (U.V.P) |
General Features |
• DC-DC / AC-DC |
AC - DC |
|
• Efficiency |
75% typ. |
|
• Dieletric withstand voltage |
• Input - Output : 3750Vac (on insul.comp.)• Input - P.E.: 1750Vac |
|
• Isolation |
• Output - P.E.: 500Vdc |
|
• See table for |
• Output voltages and current• Line and load regulation• Output ripple and noise |
|
• Cooling |
Natural convection |
|
• Operating indicator |
• Led Vout OK on front panel |
|
• Other features |
Optional:• AL - Alarm relay contact• DC - DC input for AC-DC units• DD - Output decoupl. diode for parallelconnection• INH - Inhibit input ; inhibits all outputs• PROG - Programmable Vout |
|
• Operating temperature |
0°C to 50°C |
|
• Storage temperature |
"-20°C to 85°C" |
|
• Weight |
2200g |
|
• Comply with |
• EN 50081-1• EN 61000-6-2• EN 60950-1• CE |
|
• Dimensions |
Euro Rack 3HEx36TEx172 mm |
|
• Application fiels |
Industrial application |