Input |
• Rated input voltage |
200 - 240V 3AC (180 ÷ 264V 3AC) |
|
• Line frequency |
50/60Hz |
|
• Input current (max) |
See features table |
|
• Power factor |
See features table |
|
• Input protection |
• Inrush current typ. < 30A @ Vin max, cold-start. • EMI filter • Line fuses |
|
• Input inhibit |
• (optional) High active (4.5÷15V) |
Output |
• Output voltage |
1200W |
|
• Output voltage long term stability |
Better than 1% after 24hours typ. |
|
• Adjustable voltage range |
• Vadjust trimmer |
|
• Ripple nois |
See datasheet |
|
• Output power (max) |
1200W |
|
• Temp power derating |
2%/°C (50÷60°C see diag.) |
|
• Hold up time |
See datasheet |
|
• Start up time |
<0.1 sec. |
|
• Output protections |
• Short circuit protection with automatic restart • Overcurrent protection • Overvoltage protection |
General Features |
• DC-DC / AC-DC |
AC - DC |
|
• Efficiency |
See features table |
|
• Dieletric withstand voltage |
• Conform to EN 60950-1 |
|
• Isolation |
• Output - P.E.: 500Vdc |
|
• See table for |
• Output voltage and current • Output ripple and noise |
|
• Cooling |
Forced ventilation |
|
• Operating indicator |
• Led Vout OK |
|
• Other features |
• DD - Output decoupl. diode for parallel connection |
|
• Operating temperature |
-10°C to 60°C |
|
• Storage temperature |
-25°C to +85°C |
|
• Switching frequency |
30KHz typ. |
|
• Weight |
4750g |
|
• Comply with |
• EN 50081-1 • EN 61000-6-2 • EN 60950-1 • CE |
|
• Dimensions |
246x264x80 |
|
• Application fiels |
Industrial application |